
BLOG
How non-OEM parts caused a power plant shutdown in Australia

Written By IMI Publications
March 23, 2023
The Challenge
A power station in Australia reported that one of its IMI CCI valves had failed during start up. The customer explained that the plug had separated from the stem and the failure had resulted in the unit being off-line for 24 hours while the valve was repaired. The cost of the failure to the plant was in excess of a quarter of a million Australian dollars ($180k USD).
During the root cause failure analysis of the parts at site, the IMI CCI team realised the parts that failed were non-original manufacturer (non-OEM) parts supplied by a third party. The failure of the non-OEM trim was attributed to the poor weld connection between the stem and the plug. The weld connection between the plug and stem on the failed part was tack welded on four points with poor quality welding that was insufficient to handle the stresses. In the IMI CCI design, the plug assembly has the stem threaded into the plug with a full circle weld of the screwed area of the stem and plug.
The Solution
The difference between the IMI CCI design plug/stem assembly and the non-OEM parts was explained to the customer. A final check of the customer’s spare parts inventory for the 20 installed valves was undertaken. Over 70% of the parts in the inventory were found to be non-OEM parts that had to be discarded by the customer.
The power station will place orders to gradually replace all the non-OEM parts with genuine OEM parts from IMI CCI.
The valve failure with non-OEM parts has increased the customer’s awareness of the need to use genuine spares from the OEM. While the initial cost of the OEM spares is higher, they help customers to have peace of mind, reduce their total cost of ownership and increase plant run time.
Keep in touch
Stay up to date on all the latest news and articles from IMI.

Keep in touch
Stay up to date on all the latest news and articles from IMI.


Keep in touch
Stay up to date on all the latest news and articles from IMI.
Engineering the future together
Looking for the perfect flow control solution? Our experts specialise in providing tailored solutions to meet your unique needs. Let us help you achieve optimal performance, efficiency and safety.