SolidRed 3.3
Vibration Alerts
Table of contents
There are 4 types of alerts available in the vibration use case. These are visible on the detail view of the device and in the alert tables throughout SolidRed.
ISO Based Alerts
ISO based alerts are based on the machine alert thresholds that can be edited by clicking on the pencil icon next to the item in the detail view. By doing so, a pop-up window will appear where the user can select which alerts to set on the device.

From the dropdowns, the user can select pre-defined options based on the ISO10816 or add custom alerts. For example, selecting the type General Machines and the class Medium Machine Class II will define alerts for the device as the example below:

The user can use these options as templates and edit the alerts according to their needs. Alternatively, custom alerts can be set by clicking on Add Alert. The fields the user will have to fill in are as follows:
Alert source: the measurement to be monitored. This can be RMS velocity on any of the three axes, peak acceleration on any of the three axes, or temperature (minimum, maximum, or average).
Alert label: a name to differentiate the alert and help the user identify it across SolidRed.
Severity: available options are intermediate, warning, minor, major, or critical.
Threshold value: the value that needs to be met for the alert to trigger.

Clicking on the plus icon below the delete icon on the last defined alert level will let the user add another severity level for the alert. Up to 4 severity levels can be defined within a single alert. Finally, clicking the save button will apply the defined alerts to the device in question.
Clicking on the eye icon next to the status of the ISO ISO-based alert will display a pop-up window with further insight into the alert.

In this window, the user can look at the current status, recommended actions, related measurements and FFTs to analyze the status of the monitored machine.
Device conditions
These alerts are based on the trigger thresholds configured on the device. If the threshold is configured through SolidRed, this will be available on the summary table of the alert information. For the NEON Vibration Sensor these alerts are threshold on the measurements and spectrum alerts on the FFTs.
Machine fault
Only available for NEON Vibration Sensors using communication protocol v4 onwards.
The machine fault alerts are based on the Machine Fault Indicator message of the NEON Vibration Sensor in the
common_faultone_xtwo_xn_xBearing fault
Only available for NEON Vibration Sensors using communication protocol v4 onwards.
Only available for NEON Vibration Sensors using communication protocol v4 onwards.
The bearing fault alerts are based on the Machine Fault Indicator message of the NEON Vibration Sensor in the
bearing_fault