page header background image

NEON Starting Guide

How to replace the sensor or probe

Table of contents

The NEON Vibration Sensor consists of two main parts: the transmitter and the sensor (also known as the probe). Exchanging the sensor attached to the transmitter for a new one is possible, nevertheless, certain steps must be taken to do it successfully since the transmitter must be paired with the sensor being used.

  1. Ensure the setting Allow Deactivation is set to Yes. The default configuration of the NEON vibration sensor has Allow Deactivation enabled but the user might need to send a downlink to oconfigure the device. For more information about how to generate the downlink to configure the device please refer to the Configuration section.

vibration-sensor-10

If a configuration downlink is sent to enable Allow Deactivation the user must confirm that the device changed its configuration before proceeding to step 2. The user can confirm this by monitoring when the device reboots after receiving the configuration downlink via LoRa.

  1. Deactivate the sensor by holding the button pressed for 5 seconds and, when the LED indicator turns white, release the button and press it again once. The LED will turn red indicating the device is deactivated. For more information about the deactivation procedure refer to the product manual .

  2. Disconnect the old sensor and connect the new sensor to the transmitter.

  3. Activate the device again by holding the button pressed for 5 seconds and, when the LED indicator turns white, release the button. After the activation sequence, the LED should turn green indicating a successful activation. For more information about the deactivation procedure refer to the product manual .